When water is supplied to the 600X electric control valve from the inlet end, the water flow passes through the needle valve into the main valve control chamber. When the solenoid pilot valve opens, the water in the control chamber flows out through the solenoid pilot valve and ball valve. Since the ball valve opening is greater than the needle valve opening, the pressure in the main valve control chamber is very low, keeping the main valve fully open.
When the solenoid pilot valve closes, water in the main valve control chamber cannot flow out. Pressure builds up in the control chamber, driving the diaphragm to close the main valve.
| Nominal Pressure(Mpa) | Shell Test Pressure(MPa) | Seal Test Pressure(MPa) | Applicable medium | Medium temperature(℃) |
|---|---|---|---|---|
| 1.0 | 1.5 | 1.1 | Water | 0-80 |
| 1.6 | 2.4 | 1.76 | ||
| 2.5 | 3.75 | 2.75 |